Permit: T00EL02722
Permit Details
Apply Date:
11/22/2000
Applicant:
JOSE ESTRELLA
Description:
RECONNECT:ELECTRIC:SFR
Outstanding Activity Conditions
Permit Number - T00EL02722
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC:SFR
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/22/2000 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T00EL02722
Permite Description: RECONNECT:ELECTRIC:SFR
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2000 | ELECTRIC - RECONNECT | N/A | Denied | IVRS - Inspection 0999* 1. RISER TO BE 2" RIGID AT 3' ABOVE ROOF WIRE IN RISE TO BE #4 COPPER AND PROVIDE 2' OUT OF WEATHER HEAD NEED A GROUND SYSTEM FOR SERVICE-2 GROUND RODS AND GROUND TO WATERLINE USE CORRECT TYPE CIRCUIT BREAKERS AND SIZES SEAL ALL HOLES ON SERVICE NEED A BUSHING WHERE ALL WIRES COME THUR BOX NEED 2 SUPPORTS ON RISER THERE IS TO MUCH OPEN WIRING THRU OUT HOUSE TO RELEASE POWER GENERATOR NOT TO BE CONNECTED TO HOUSE WIRING ONLY TO SEPERATE CORD SUGGEST YOU OBTAIN ELECTRICAL CONTRACTOR TO CORRECT WIRING. CALLED OWNER JOSE ESTRELLA TO SAY AFTER INSPECTION FOR RECONNECT AT 1608 S FREMONT, T00EL02722 AFTER COMING INTO OFFICE TO CHECK PREVIOUS RECORDS AT THIS ADDRESS. THERE HAS NEVER BEEN ANY TYPE OF PERMIT OBTAINED FOR NEW WIRING FOR MOST OF RESIDENCE, RECORDS SHOW NO PERMITS EVER DRAWN. NOTIFIED MR. ESTRELLA OF THIS SITUATION HE STATED HE HAD REWIRED THE HOUSE HIMSELF AND DID NOT KNOW HE WAS REQUIRED TO OBTAIN A PERMIT AND INSPECTION. SINCE THE WIRING WAS NOT INSPECTED I NOTIFIED HIM THERE COULD BE NO CLEARANCE IF ALL OTHER ITEM CORRECTED |
| 11/22/2000 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999* RISER TO BE 2" RIGID AT 3' ABOVE ROOF WIRE IN RISE TO BE #4 UPPER AND PROVIDE 2' OUT OF WEATHER HEAD NEED A GROUND SYSTEM FOR SERVICE-2GROUND RODS AND GROUND TO WATER LINE USE CORRECT TYPE CIRCUIT BREAKERS AND SIZES SEAL ALL HOLES ON SERVICE NEED A BUSHING WHERE ALL WIRES COME THUR BOX NEED 2 SUPPORTS ON RISER THERE IS TO MUCH OPEN WIRING THRU OUT HOUSE TO RELEASE POWER GENERATOR NOT TO BE CONNECTED TO HOUSE WIRING ONLY TO SEPERATE CORD SUGGEST YOU OBTAIN ELECTRICAL CONTRACTOR TO CORRECT WIRING |