Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
| 11/22/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* RISER TO BE 2" RIGID AT 3' ABOVE ROOF WIRE IN RISE TO BE #4 UPPER AND PROVIDE 2' OUT OF WEATHER HEAD NEED A GROUND SYSTEM FOR SERVICE-2GROUND RODS AND GROUND TO WATER LINE USE CORRECT TYPE CIRCUIT BREAKERS AND SIZES SEAL ALL HOLES ON SERVICE NEED A BUSHING WHERE ALL WIRES COME THUR BOX NEED 2 SUPPORTS ON RISER THERE IS TO MUCH OPEN WIRING THRU OUT HOUSE TO RELEASE POWER GENERATOR NOT TO BE CONNECTED TO HOUSE WIRING ONLY TO SEPERATE CORD SUGGEST YOU OBTAIN ELECTRICAL CONTRACTOR TO CORRECT WIRING |