Permit: T00EL02722

Parcel: 12912021B


Addresses:

1608 S FREMONT AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/12/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
11/22/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
RISER TO BE 2" RIGID AT 3' ABOVE ROOF
WIRE IN RISE TO BE #4 UPPER AND PROVIDE 2' OUT OF WEATHER HEAD
NEED A GROUND SYSTEM FOR SERVICE-2GROUND RODS AND GROUND TO WATER LINE
USE CORRECT TYPE CIRCUIT BREAKERS AND SIZES
SEAL ALL HOLES ON SERVICE
NEED A BUSHING WHERE ALL WIRES COME THUR BOX
NEED 2 SUPPORTS ON RISER THERE IS TO MUCH OPEN WIRING THRU OUT HOUSE TO RELEASE POWER
GENERATOR NOT TO BE CONNECTED TO HOUSE WIRING ONLY TO SEPERATE CORD
SUGGEST YOU OBTAIN ELECTRICAL CONTRACTOR TO CORRECT WIRING