Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
3734 E SHEPHERD PL
Apply Date:
08/30/2000
Applicant:
MARIA ELENA DELGADO
Description:
UPGRADE:ELECTRICAL FROM 30AMP TO 200 AMP

Permit Reviews

Permit Number - T00EL02111
Permit Status: Expired
Permit Description: UPGRADE:ELECTRICAL FROM 30AMP TO 200 AMP
Start Date Submittal Complete Date Status  
08/30/2000 ELECTRICAL 08/30/2000 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T00EL02111
Permit Status: Expired
Permit Description: UPGRADE:ELECTRICAL FROM 30AMP TO 200 AMP
Total Outstanding Activity Conditions - 1
Date Name
08/30/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T00EL02111
Permite Description: UPGRADE:ELECTRICAL FROM 30AMP TO 200 AMP
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
09/15/2000 ELECTRIC - SERVICE UPGRADE N/A Denied IVRS - Inspection 0999*
IDENTIFY NEUTRAL CONDUTOR AT WEATHERHEAD AND INSIDE METER COMPARTMENT WHITE OR NATURAL GREY
2. INSTALL WATER BOND
3. INSTALL GAS BOND
4. J-BOXES OVERFILLED
5. SEAL UNUSED KNOCKOUTS AT BOTTOM OF PANEL
6. USE PROPER FITTING WHERE GROUNDING ELECTRODE CONDUCTOR ENTERS PANEL
7. GROUNDING ELECTRODE CONDUCTOR CAN'T BE DOUBLE LUGGED WITH NEUTRAL CONDUCTOR AT METER
8. SET SCREW FITTINGS ARE NOT WEATHER PROOF
9. WIRES TOO SHORT AT WEATHERHEAD
10. NEED PERMIT FOR REAR ADDITION
11. 1X4 NOT ACCEPTABLE FOR SECURING RISER
12. NEED ADDRESS ON METER BASE PER T.E.P
13. N.M. CABLE IS NOT TO BE INSTALLED IN CONDUIT SYSTEM
14. LIC. CONTRACTOR WITH C-11 LIC. TO FINISH JOB
8.
09/20/2000 ELECTRIC - FINAL N/A Partial Approval IVRS - Inspection 0000*
OK TO CLEAR SER INCREASE