Permit: T00EL02111

Parcel: 130121470


Addresses:

3734 E SHEPHERD PL

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/20/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
OK TO CLEAR SER INCREASE
09/19/2000 ELECTRIC - FINAL Denied PUT ADDRESS ON SERVICE PERMANENT
NEED 2 SUPPORTS ON RISER BELOW ROOF
USE ROMEX CONNECTOR FOR GROUND WIRE BELOW SERVICE AND SEAL EXTRA HOLE
TRANSFER TO OLD SERVICE INCORRECT MUST GO TO EXISTING SERVICE
ROOF JACK ON 2" RISE
09/15/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999$
REJECTED
ADDRESS METER
BOND WATER AND GAS
ALL OUTSIDE FITTINGS ON PIPE TO BE WEATHER PROOF
ID NEUTRAL SERVICE ENTRANCE CONDUCTORS
BOX LOCKED CANNOT INSPECT
STAPLE GROUND WIRE TO WALL
DRIVE GROUND RODS TO BELOW GRADE
NEED 2 SUPPORTS BELOW ROOF ON RISER
NEED ROOF JACK SUGGEST YOU HIRE A LICENSED ELECTRICAL CONTRACTOR
09/15/2000 ELECTRIC - FINAL Denied
09/13/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
09/11/2000 ELECTRIC - FINAL Denied NEED 2ND GROUND ROD.