Permit: T00EL02111

Parcel: 130121470


Addresses:

3734 E SHEPHERD PL

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/15/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
IDENTIFY NEUTRAL CONDUTOR AT WEATHERHEAD AND INSIDE METER COMPARTMENT WHITE OR NATURAL GREY
2. INSTALL WATER BOND
3. INSTALL GAS BOND
4. J-BOXES OVERFILLED
5. SEAL UNUSED KNOCKOUTS AT BOTTOM OF PANEL
6. USE PROPER FITTING WHERE GROUNDING ELECTRODE CONDUCTOR ENTERS PANEL
7. GROUNDING ELECTRODE CONDUCTOR CAN'T BE DOUBLE LUGGED WITH NEUTRAL CONDUCTOR AT METER
8. SET SCREW FITTINGS ARE NOT WEATHER PROOF
9. WIRES TOO SHORT AT WEATHERHEAD
10. NEED PERMIT FOR REAR ADDITION
11. 1X4 NOT ACCEPTABLE FOR SECURING RISER
12. NEED ADDRESS ON METER BASE PER T.E.P
13. N.M. CABLE IS NOT TO BE INSTALLED IN CONDUIT SYSTEM
14. LIC. CONTRACTOR WITH C-11 LIC. TO FINISH JOB
8.
09/11/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*