Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* IDENTIFY NEUTRAL CONDUTOR AT WEATHERHEAD AND INSIDE METER COMPARTMENT WHITE OR NATURAL GREY 2. INSTALL WATER BOND 3. INSTALL GAS BOND 4. J-BOXES OVERFILLED 5. SEAL UNUSED KNOCKOUTS AT BOTTOM OF PANEL 6. USE PROPER FITTING WHERE GROUNDING ELECTRODE CONDUCTOR ENTERS PANEL 7. GROUNDING ELECTRODE CONDUCTOR CAN'T BE DOUBLE LUGGED WITH NEUTRAL CONDUCTOR AT METER 8. SET SCREW FITTINGS ARE NOT WEATHER PROOF 9. WIRES TOO SHORT AT WEATHERHEAD 10. NEED PERMIT FOR REAR ADDITION 11. 1X4 NOT ACCEPTABLE FOR SECURING RISER 12. NEED ADDRESS ON METER BASE PER T.E.P 13. N.M. CABLE IS NOT TO BE INSTALLED IN CONDUIT SYSTEM 14. LIC. CONTRACTOR WITH C-11 LIC. TO FINISH JOB 8. |
|
| 09/11/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* |