Permit: T00EL00602
Permit Details
Apply Date:
03/09/2000
Applicant:
KAP ELECTRIC INC ,
Description:
NEW SERVICE:ELECTRIC
Contractors:
- KAP ELECTRIC INC ,
Outstanding Inspections
Permit Status: Expired
Permit Number: T00EL00602
Permite Description: NEW SERVICE:ELECTRIC
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/06/2000 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection 0999* 1. MUST HAVE A COMPLETE SET OF CITY APPROVED FPLANS MUST BE ACCURATE 2. RISER CROOKED AND IMPROPERLY FASTENED TO WALL AND IMPROPER SEAL FITTINGS 3. NEED GROUNDING BUSHINGGS AND BONDING JUMPERS THROUGH OUT SUPPLY SIDE RACEWAYS AND FITTINGS 4. TERMIANL BUS IN GUTTER NOT CLEAN 5. MAIN GROUNDING ELECTRODE CONDUTOR TERMINATION MUST BE IN SUPPLY SIDE GUTTER AT NEUTRAL AND BONDED TO EQUIPMENT 6. EXPOSE RODS, WATER AND GAS BOND 7. NEED PERMANENT ADDRESS PER CITY AMENDMENT AT EACH SERVICE 8. EXPOSE UNDERGROUND ELECTRICAL 9. ONLY ONE SERVICE DROP ALLOWED 10 SPLIT BOLT CONNECTOR ONLY GOOD FOR 2 CONDUCTOR |