Permit: T00EL00602

Parcel: 117070280


Addresses:

235 E 15TH ST


Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T00EL00602

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Denied

Date Description Inspector Results Comments
07/06/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
1. MUST HAVE A COMPLETE SET OF CITY APPROVED FPLANS MUST BE ACCURATE
2. RISER CROOKED AND IMPROPERLY FASTENED TO WALL AND IMPROPER SEAL FITTINGS
3. NEED GROUNDING BUSHINGGS AND BONDING JUMPERS THROUGH OUT SUPPLY SIDE RACEWAYS AND FITTINGS
4. TERMIANL BUS IN GUTTER NOT CLEAN
5. MAIN GROUNDING ELECTRODE CONDUTOR TERMINATION MUST BE IN SUPPLY SIDE GUTTER AT NEUTRAL AND BONDED TO EQUIPMENT
6. EXPOSE RODS, WATER AND GAS BOND
7. NEED PERMANENT ADDRESS PER CITY AMENDMENT AT EACH SERVICE
8. EXPOSE UNDERGROUND ELECTRICAL
9. ONLY ONE SERVICE DROP ALLOWED
10 SPLIT BOLT CONNECTOR ONLY GOOD FOR 2 CONDUCTOR