Permit: T00CM05494
Permit Details
Apply Date:
11/09/2000
Applicant:
HANSON, JAY VAN
Description:
ADDITION:CLASSROOMS
Architects:
- HANSON, JAY VAN
Contractors:
- CARNES CONSTRUCTION INC ,
Permit Reviews
Permit Number - T00CM05494
Permit Status: C of o
Permit Description: ADDITION:CLASSROOMS
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/01/2001 | RESUBMITTAL | 03/29/2001 | COMPLETED |
| 03/29/2001 | RESUBMITTAL | 04/10/2001 | COMPLETED |
| 04/10/2001 | RESUBMITTAL | 04/10/2001 | COMPLETED |
| 11/09/2000 | COMMERCIAL NEW | 03/29/2001 | COMPLETED |
| 11/09/2000 | SITE | 03/29/2001 | COMPLETED |
Completed Inspections
Permit Status: C of o
Permit Number: T00CM05494
Permit Description: ADDITION:CLASSROOMS
Total Completed Inspections - 27
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2001 | FRAMING | DWITT | Approved | IVRS - Inspection 0000* |
| 06/01/2001 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | |
| 06/01/2001 | SHEET ROCK NAILING | DWITT | Approved | IVRS - Inspection 0000*WAITING FOR PACHOMETER RESULTS. |
| 06/06/2001 | PLUMBING - SEWER HCS CONNECT | RMYERS | Approved | IVRS - Inspection 0000* |
| 06/06/2001 | PLUMBING - YARD WTR LINE/TEST | RMYERS | Approved | IVRS - Inspection 0000*1)SEWER CONNECTION OK. TIE-IN OK.TRANSITION FITTINGS OK.2)WATER TEST OK.3)OK TO DRAIN AND COVER.4)LAND WATER LINE/TEST TIE-IN TO EXISTING OK PRESSURE TEST OK. |
| 07/16/2001 | MECHANICAL - INTERMEDIATE | CWILLIAM | Approved | IVRS - Inspection 0000* |
| 07/16/2001 | ELECTRIC - UNDERGROUND | MCAPISTR | Approved | IVRS - Inspection 0000* |
| 07/16/2001 | ELECTRIC - UFER | MCAPISTR | Approved | IVRS - Inspection 0000* |
| 07/16/2001 | BUILDING ABOVE CEILING | DWITT | Approved | IVRS - Inspection 0000* |
| 07/25/2001 | PLUMBING - PROGRESS | RMYERS | Approved | IVRS - Inspection 0000*1.) DONT FORGET TO REDLINE "AS BUILT" FOR CONNECTION TO EXISTING ROOF DRAIN 2.) ABOVE CEILING OK 3.) INTERMEDIATE OK 4.) PROGRESS OK 5.) WILL CHECK GAS PRESSURE TEST AND FINAL CONNECTIONS WHEN YOU CALL IN FOR FINAL. |
| 07/25/2001 | PLUMBING - ABOVE CEILING | RMYERS | Approved | IVRS - Inspection 0000* |
| 07/25/2001 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection 0000* |
| 07/31/2001 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | 1.)MEDIUM PRESSURE GAS PIPE UP TO UNITS FROM METER 60#TEST OK. 2.) LOW PRESSURE TEST FROM REGULATOR TO UNITS OK 10# AIR TEST OK 3.) INSTALL MISSING UNISTRUT CLAMPS INSTALL REGULATOR WILL INSPECT ON FINAL. |
| 08/08/2001 | SIGN - FINAL | DJOHNSTO | Approved | IVRS - Inspection 0000* |
| 08/09/2001 | ELECTRIC - FINAL | MCAPISTR | Approved | IVRS - Inspection 0000*C OF O OK |
| 08/09/2001 | ELECTRIC - ABOVE CEILING | MCAPISTR | Approved | IVRS - Inspection 0000* |
| 08/10/2001 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection 0000*OK FOR C OF O INSPECTION ON FIRE DAMPERS IN CORRIDORS. |
| 08/10/2001 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | |
| 08/10/2001 | ELECTRIC - INTERMEDIATE | MCAPISTR | Approved | |
| 08/28/2001 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection 0000* |
| 08/28/2001 | BUILDING - FINAL | LHANLY | Approved | IVRS - Inspection 0000* |
| 08/29/2001 | PERMIT FINALED | LHANLY | Approved | |
| 08/29/2001 | ROOF NAILING | LHANLY | Approved | |
| 08/29/2001 | REINFORCED MASONRY PRE-GROUT | LHANLY | Approved | |
| 08/29/2001 | BUILDING PRE-SLAB | LHANLY | Approved | |
| 08/29/2001 | STEM WALL/RETAINING WALL | LHANLY | Approved | |
| 08/29/2001 | EXCAVATION/LAYOUT REBAR & ZON | LHANLY | Approved |