Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T00CM05494
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/25/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 01/31/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/31/2001 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 02/06/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide a complete civil site plan with a Basis of Elevation, UP & DOWN stream M.H. Rim Elev., Inverts, F.F.E., Water & Sewer lines and size of same. 2. Provide S.O.Valves as noted on P2.1. 3. Provide a complete waste line Isometric drawing on the plan. |
| 02/06/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Model Energy Code calculations not with plan set. |
| 02/08/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/09/2001 | MARK TITUS | WATER | REVIEW | Approved | |
| 02/12/2001 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/13/2000 | PATRICIA GEHLEN | ZONING | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/29/2001 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 02/12/2001 | TAMI ACHONG | REJECT SHELF | Completed |
| 02/12/2001 | DELMA ROBEY | REJECT SHELF | Completed |