Permit: T00CM02316
Permit Details
Status:
Expired
Type:
COMMERCIAL NEW
Address:
12615 W MILE WIDE RD
Address NEW:
12615 W MILE WIDE RD
Apply Date:
05/05/2000
Applicant:
CITY OF TUCSON
Description:
WELL SITE/FENCING/CONTROL BUILDING/20 ANTENNA 8.67 x 8.67 MASONRY CONTROL BUILDING W/ CONCRETEROOF
Permit Reviews
Permit Number - T00CM02316
Permit Status: Expired
Permit Description: WELL SITE/FENCING/CONTROL BUILDING/20 ANTENNA 8.67 x 8.67 MASONRY CONTROL BUILDING W/ CONCRETEROOF
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/30/2001 | REVISION | 02/13/2001 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T00CM02316
Permit Status: Expired
Permit Description: WELL SITE/FENCING/CONTROL BUILDING/20 ANTENNA 8.67 x 8.67 MASONRY CONTROL BUILDING W/ CONCRETEROOF
Total Outstanding Activity Conditions - 2
| Date | Name |
|---|---|
| 06/15/2000 | SPECIAL INSPECTION FOR CONCRETE IS REQUIRED.. |
| 06/15/2000 | SPECIAL INSPECTION FOR STRUCTURAL MASONRY IS REQUIRED. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T00CM02316
Permite Description: WELL SITE/FENCING/CONTROL BUILDING/20 ANTENNA 8.67 x 8.67 MASONRY CONTROL BUILDING W/ CONCRETEROOF
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2001 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0935*1. BOND GUTTER WITH FUSES 250-96 2. BONDING DEVICE NEEDED AT CONCENTRICS 250-97 3. PLANS DO NOT SHOW SURGE ARRESTORS ON BREKERS OR FUSES RATED HIGHER THAN CONDUCTOR CAPACITY FUSE & BREAKERS ACCORDINGLY 4. TIGHTEN ALL SEALTIGHT FITTINGS AT INJECTOR STATION |
Completed Inspections
Permit Status: Expired
Permit Number: T00CM02316
Permit Description: WELL SITE/FENCING/CONTROL BUILDING/20 ANTENNA 8.67 x 8.67 MASONRY CONTROL BUILDING W/ CONCRETEROOF
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2000 | REINFORCED MASONRY PRE-GROUT | AMATHIES | Approved | IVRS - Inspection 0000* |
| 11/17/2000 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection 0000* |
| 03/05/2001 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection 0000* 1) PERMANENT ADDRESS ON SERVICE 2) INSTALL PVC 3/4" ON UFER OR IF USING RIGID INSTALL CLAMP AT END OF 3/4" RIGID BRASS TYPE 3) SCRAPE OFF PAINT ON GUTTER AND 600AMP DISCONNECT (GROUNDS) 4) EXTEND BOND BUSHING GROUND TO 600AMP ENCLOSURE 5) INSTALL SCREW ON 30AMP DISCONNECT, GREEN GROUND SCREW |
| 03/06/2001 | ELECTRIC - TEMPORARY SERVICE | RMAJUTA | Approved | IVRS - Inspection 0000* |
| 03/06/2001 | ELECTRIC - CABLE DROP | RMAJUTA | Approved | IVRS - Inspection 0000* |
| 03/13/2001 | BUILDING - FINAL | AMATHIES | Approved | IVRS - Inspection 0000* |