Permit Details

Status:
Expired
Type:
COMMERCIAL NEW
Address NEW:
12615 W MILE WIDE RD
Apply Date:
05/05/2000
Applicant:
CITY OF TUCSON
Description:
WELL SITE/FENCING/CONTROL BUILDING/20 ANTENNA 8.67 x 8.67 MASONRY CONTROL BUILDING W/ CONCRETEROOF

Permit Reviews

Permit Number - T00CM02316
Permit Status: Expired
Permit Description: WELL SITE/FENCING/CONTROL BUILDING/20 ANTENNA 8.67 x 8.67 MASONRY CONTROL BUILDING W/ CONCRETEROOF
Start Date Submittal Complete Date Status  
01/30/2001 REVISION 02/13/2001 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T00CM02316
Permit Status: Expired
Permit Description: WELL SITE/FENCING/CONTROL BUILDING/20 ANTENNA 8.67 x 8.67 MASONRY CONTROL BUILDING W/ CONCRETEROOF
Total Outstanding Activity Conditions - 2
Date Name
06/15/2000 SPECIAL INSPECTION FOR CONCRETE IS REQUIRED..
06/15/2000 SPECIAL INSPECTION FOR STRUCTURAL MASONRY IS REQUIRED.

Outstanding Inspections

Permit Status: Expired
Permit Number: T00CM02316
Permite Description: WELL SITE/FENCING/CONTROL BUILDING/20 ANTENNA 8.67 x 8.67 MASONRY CONTROL BUILDING W/ CONCRETEROOF
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
04/17/2001 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0935*1. BOND GUTTER WITH FUSES 250-96 2. BONDING DEVICE NEEDED AT CONCENTRICS 250-97 3. PLANS DO NOT SHOW SURGE ARRESTORS ON BREKERS OR FUSES RATED HIGHER THAN CONDUCTOR CAPACITY FUSE & BREAKERS ACCORDINGLY 4. TIGHTEN ALL SEALTIGHT FITTINGS AT INJECTOR STATION

Completed Inspections

Permit Status: Expired
Permit Number: T00CM02316
Permit Description: WELL SITE/FENCING/CONTROL BUILDING/20 ANTENNA 8.67 x 8.67 MASONRY CONTROL BUILDING W/ CONCRETEROOF
Total Completed Inspections - 6
Date Description Inspector Results Comments
09/27/2000 REINFORCED MASONRY PRE-GROUT AMATHIES Approved IVRS - Inspection 0000*
11/17/2000 ELECTRIC - UNDERGROUND DSANTACR Approved IVRS - Inspection 0000*
03/05/2001 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection 0000* 1) PERMANENT ADDRESS ON SERVICE 2) INSTALL PVC 3/4" ON UFER OR IF USING RIGID INSTALL CLAMP AT END OF 3/4" RIGID BRASS TYPE 3) SCRAPE OFF PAINT ON GUTTER AND 600AMP DISCONNECT (GROUNDS) 4) EXTEND BOND BUSHING GROUND TO 600AMP ENCLOSURE 5) INSTALL SCREW ON 30AMP DISCONNECT, GREEN GROUND SCREW
03/06/2001 ELECTRIC - TEMPORARY SERVICE RMAJUTA Approved IVRS - Inspection 0000*
03/06/2001 ELECTRIC - CABLE DROP RMAJUTA Approved IVRS - Inspection 0000*
03/13/2001 BUILDING - FINAL AMATHIES Approved IVRS - Inspection 0000*

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW