Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/05/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* 1) PERMANENT ADDRESS ON SERVICE 2) INSTALL PVC 3/4" ON UFER OR IF USING RIGID INSTALL CLAMP AT END OF 3/4" RIGID BRASS TYPE 3) SCRAPE OFF PAINT ON GUTTER AND 600AMP DISCONNECT (GROUNDS) 4) EXTEND BOND BUSHING GROUND TO 600AMP ENCLOSURE 5) INSTALL SCREW ON 30AMP DISCONNECT, GREEN GROUND SCREW | |
| 02/15/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* COMPLETE WIRING OF SERVICE AND ASSOCIATED EQUIPMENT ETC.. RECALL WHEN READY |