Date Description Inspector Results Comments
03/05/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000* 1) PERMANENT ADDRESS ON SERVICE 2) INSTALL PVC 3/4" ON UFER OR IF USING RIGID INSTALL CLAMP AT END OF 3/4" RIGID BRASS TYPE 3) SCRAPE OFF PAINT ON GUTTER AND 600AMP DISCONNECT (GROUNDS) 4) EXTEND BOND BUSHING GROUND TO 600AMP ENCLOSURE 5) INSTALL SCREW ON 30AMP DISCONNECT, GREEN GROUND SCREW
02/15/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* COMPLETE WIRING OF SERVICE AND ASSOCIATED EQUIPMENT ETC..
RECALL WHEN READY