Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/17/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935*1. BOND GUTTER WITH FUSES 250-96 2. BONDING DEVICE NEEDED AT CONCENTRICS 250-97 3. PLANS DO NOT SHOW SURGE ARRESTORS ON BREKERS OR FUSES RATED HIGHER THAN CONDUCTOR CAPACITY FUSE & BREAKERS ACCORDINGLY 4. TIGHTEN ALL SEALTIGHT FITTINGS AT INJECTOR STATION |
| 04/03/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* 1) WORKING CLEARANCE IN FRONT OF GUTTER WITH FUSES 2) NEED MANUFACTURERS INSTRUCTIONS FOR SURLE ARESTOR TO DETERMINE BREAKER SIZE (#14 AWG ON 30 AMP BREAKER) 3) PROTECT SEAL TITE PASSING THRU TO WELL METERS 4) LOOSE FITTINGS 5) INSTALL COVERS CORRECTLY INJECTOR STATION 6) NEED REVISED PLANS FOR THIS SITE |
| 03/13/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |