Inspection Status: Partial Pass
Inspection History: COT - FCON - Alarm - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 10/23/2026 |
COT - FCON - Alarm - Final |
|
Partial Pass |
All defunct devices shall be removed. ADA room 111 notifications not working. Smoke 34 labeled incorrectly. Ensure central station has accurate descriptions. Test elevator heats/smokes ensure elevator is not disabled while between floors. ROC and 1st year annual inspection report. |