Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Inspections
Type:
Fire Construction Permit
Address NEW:
4975 S LIBERTY AV
Apply Date:
03/20/2026
Applicant:
Weslee Upchurch
Description:
PROVIDE NEW FIRE ALARM SYSTEM FOR "CASA DEL PUEBLO SENIOR COMMUNITY". FIRE CONTROL PANEL AND ALL INITIATIATING AND NOTIFICATION DEVICES WILL BE NEW. NEW 18AH BATTERIES TO BE INSTALLED IN BOTTOM OF FACP CABINET.

Permit Reviews

Permit Number - TF-FCP-0326-00193
Permit Status: Inspections
Permit Description: PROVIDE NEW FIRE ALARM SYSTEM FOR "CASA DEL PUEBLO SENIOR COMMUNITY". FIRE CONTROL PANEL AND ALL INITIATIATING AND NOTIFICATION DEVICES WILL BE NEW. NEW 18AH BATTERIES TO BE INSTALLED IN BOTTOM OF FACP CABINET.
Start Date Submittal Complete Date Status  
05/05/2026 FIRE CONSTRUCTION REVIEW v.2 05/20/2026 APPROVED Review Details
06/05/2026 FIRE CONSTRUCTION REVIEW REVISION v.1 06/15/2026 APPROVED Review Details
03/23/2026 FIRE CONSTRUCTION REVIEW v.1 04/16/2026 REQUIRES RESUBMIT Review Details

Outstanding Inspections

Permit Status: Inspections
Permit Number: TF-FCP-0326-00193
Permite Description: PROVIDE NEW FIRE ALARM SYSTEM FOR "CASA DEL PUEBLO SENIOR COMMUNITY". FIRE CONTROL PANEL AND ALL INITIATIATING AND NOTIFICATION DEVICES WILL BE NEW. NEW 18AH BATTERIES TO BE INSTALLED IN BOTTOM OF FACP CABINET.
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
10/23/2026 COT - FCON - Alarm - Final N/A Partial Pass All defunct devices shall be removed. ADA room 111 notifications not working. Smoke 34 labeled incorrectly. Ensure central station has accurate descriptions. Test elevator heats/smokes ensure elevator is not disabled while between floors. ROC and 1st year annual inspection report.

Documents

File Name Document Type  
MD1172_FA_C_V1.PDF DOCUMENTS VIEW
MD1172 CDP_FA_B_V2.PDF DOCUMENTS VIEW
MD1172_FA_B_V1.PDF DOCUMENTS VIEW