Permit: TD-DEV-0725-00181

Parcel: 141186020


Addresses:

10000 E OLD VAIL RD

Inspection Status: Partial Pass

Inspection History

Date Description Inspector Results Comments
04/27/2026 Partial Pass 12" HDPE drain pipe on North side from trench drain to stormwater basin is installed (not yet punched through wall or connected to trench drain) at proper depth and slope, already backfilled.
05/14/2026 Partial Pass OK to backfill the 8 inch roof drain 20 feet
06/04/2026 Partial Pass OK to pour the concrete at the loading dock area around the storm drain
08/13/2026 Re-inspection required Scuppers in sidewalk on West side of main entrance drive from Old Vail: inverts are too high, approximately 4 inches higher than the pavement/curbcut. Scupper invert needs to be lower than pavement height per plans. See attached photos showing scupper higher than pavement and refer to plans for spot elevations of pavement and scuppers.