Permit: TD-DEV-0723-00310

Parcel: 12618111E


Addresses:

3925 E 22ND ST

Inspection Status: Passed

Inspection History: For trash and recycling enclosures

Date Description Inspector Results Comments
05/06/2026 For trash and recycling enclosures Passed
12/10/2025 For trash and recycling enclosures Not Ready 12/10/25
I talked to mason and superintendent about the specifics of TSM double Refuse enclosure and inspections needed. However Rebar reinforcing not in place yet in footer.
12/11/2025 For trash and recycling enclosures Re-inspection required (with fee) Bollards not in place for pour. 2nd not ready.
12/12/2025 For trash and recycling enclosures Partial Pass 12/12/25
Footer dimensions and reinforcing correct. Bollard footers correct. Footer okay to pour.
Request inspection for pregrout when wall is built per plan and ready with bond beam at top. Use ladders horizontal reinforcement at 16" oc.
12/19/2025 For trash and recycling enclosures Partial Pass Okay to pour enclosure slab.