Inspection Status: Re-inspection required
Inspection History: COT - HCBU - Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 04/23/2026 |
COT - HCBU - Framing |
|
Re-inspection required |
4-23-26: have architect of record submit an RFI with all related details showing change from wood to metal framing at classrooms. |
| 05/05/2026 |
COT - HCBU - Framing |
|
Re-inspection required |
5-5-26: classroom's 101-106. Add shot within 6" at the ends of each plate & 16" o.c. thereafter. Entire south wall of 101 is missing shot pins, add mud rings for thermostat wires at several 1st floor classrooms. Add shot pins to marked areas and a screw to top plate of king stud of room 104. |
| 05/15/2026 |
COT - HCBU - Framing |
|
Re-inspection required |
5-15-26: Classroom's 201-206-add shot pins 16" o.c. at sill plate and screws at marked locations (stud to sill lip). |
| 05/18/2026 |
COT - HCBU - Framing |
|
Partial Pass |
5/18/2026 all corrections were made from previous inspection. Okay to proceed progress areas. |