Inspection Status: Re-inspection required

Inspection History: COT - HCEL - Electrical Progress  

Permit Number - TC-COM-1223-02905

Inspection Description - COT - HCEL - Electrical Progress  

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
06/27/2024 COT - HCEL - Electrical Progress   Re-inspection required 6/27/24: copper piping shall not make contact with dissimilar metals (MC cable making contact throughout, Makings contact at top plates throughout), properly support copper piping throughout, DWV not under test, properly support Flex duct throughout, properly support MC cable through (off of grid), ensure that all light fixtures and A/C diffusers are properly supported by seismic wiring.
07/15/2024 COT - HCEL - Electrical Progress   Passed