Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Parcel: 11504495A


Addresses:

1001 N PARK AV


Inspection Status: Partial Pass

Inspection History: COT - FCON - Fire - Final

Permit Number - TC-COM-1222-00337

Inspection Description - COT - FCON - Fire - Final

Inspection Status - Partial Pass

Date Description Inspector Results Comments
05/08/2025 COT - FCON - Fire - Final Partial Pass Fire pump pressures fixed, standpipe caps, stairwell 2 gate mag lock, fire alarm monitoring permit approved. Ok for TCO level 4
05/13/2025 COT - FCON - Fire - Final Partial Pass FDC sign, sprinkler calc. plates, OK for TCO level 4
07/11/2025 COT - FCON - Fire - Final Partial Pass FDC sign wording corrected, work table for FCC, stairwell 1 floor 10M exit sign repaired, stairwell 2 exit corridor dust cover on smoke detector.
07/14/2025 COT - FCON - Fire - Final Passed