Inspection History: COT - HCBU - Building Above Ceiling
Permit Number - TC-COM-1122-00067
Inspection Description - COT - HCBU - Building Above Ceiling
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2024 | COT - HCBU - Building Above Ceiling | Re-inspection required | 2/1/24: above ceiling in drop ceiling area need corrections made. Seismic wire making contact with Copper piping needs to be taped off, hangers for copper piping need to be coated or piping needs to be tapped in order to stop dissimilar material from making contact, j-boxes must be made up and labeled. | |
02/06/2024 | COT - HCBU - Building Above Ceiling | Passed | Approved, corrections addressed, okay to cover progress areas |