| 06/27/2025 | COT - HCEL - Electrical Underground | Partial Pass | X3 2” for future power and x1 is for future data. Heading East of pad. Approximately 90’. Okay to backfill progress areas. 6/27/2025 | |
| 09/08/2025 | COT - HCEL - Electrical Underground | Partial Pass | 9-8-25: verified trench depth on a couple of 4" Schedule 40 conduits from SES-J2. Okay to backfill approximately 375' of open trench. | |
| 09/12/2025 | COT - HCEL - Electrical Underground | Partial Pass | 9/12/25: electrical underground for (8)4" conduit schedule 40 from transformer to SES secondaries approved. Ok to proceed with backfill. Shading required. Electrical Caution tape required in trench 12" below finish grade. | |
| 09/26/2025 | COT - HCEL - Electrical Underground | Partial Pass | 9-26-25: verified trench depth for 2- 4" schedule 40 electrical primary conduits from “J2” equipment, west to existing TEP manhole. Okay to backfill approximately 160' of trench. |