Inspection Status: Not Ready

Inspection History: COT - LCEL - Electrical Final 

Date Description Inspector Results Comments
04/10/2025 COT - LCEL - Electrical Final  Not Ready
COT - LCEL - Electrical Final  Re-inspection required 6-12-26: gfci receptacle required at storage room- receptacle within 6' of water.
06/25/2026 COT - LCEL - Electrical Final  Re-inspection required 6-25-26: label junction box above ceiling at I.T. room, submit an updated mechanical RFI for HVAC units installed on south eastern section of building. Units are smaller than what plans originally called for and are being over amped. Max breaker should be 31 but there is a 35 amp breaker at panel instead. Insulate copper water line at east side of building with a minimum of R3. Submit all required 3rd party reports to the city for review & approval. Permit cannot be finalized until all conditions are satisfied.
07/01/2026 COT - LCEL - Electrical Final  Passed 7-1-26: electrical final approved.