Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Not Ready
Inspection History: COT - LCEL - Electrical Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 10/16/2023 |
COT - LCEL - Electrical Intermediate |
|
Not Ready |
Not ready. |
| 11/16/2023 |
COT - LCEL - Electrical Intermediate |
|
Not Ready |
Need to verify underground to EV charger location, covered w/o inspection |
| 11/20/2023 |
COT - LCEL - Electrical Intermediate |
|
Passed |
|