Parcel: 14106020D


Addresses:

7345 E VALENCIA RD


Inspection Status: Partial Pass

Inspection History: COT - HCEL - Electrical Underground 

Permit Number - TC-COM-0523-01382

Inspection Description - COT - HCEL - Electrical Underground 

Inspection Status - Partial Pass

Date Description Inspector Results Comments
02/07/2024 COT - HCEL - Electrical Underground  Partial Pass 2/7/24: partial for under ground electric
COT - HCEL - Electrical Underground  Partial Pass 2/14/24: partial for under ground electric east of building okay to backfill trench
02/23/2024 COT - HCEL - Electrical Underground  Partial Pass 2/23/24: dock opening 1-4 okay to cover 3/4 conduit in wall
02/28/2024 COT - HCEL - Electrical Underground  Partial Pass 2/28/24: main electric room, east side of building column line 4 panel feeders okay to cover
03/07/2024 COT - HCEL - Electrical Underground  Partial Pass 2/7/24: partial for under ground electric
2/14/24: partial for under ground electric east of building okay to backfill trench
2/23/24: dock opening 1-4 okay to cover 3/4 conduit in wall
2/28/24: main electric room, east side of building column line 4 panel feeders okay to cover
3/7/24: main electric room electrical underground complete. Ok to backfill.
09/18/2024 COT - HCEL - Electrical Underground  Partial Pass Secondary feeders for Transformer 1 and 2. Cam locks for portable generators and permanent generator. Okay to backfill. Shading required. 9/18/2024
10/07/2024 COT - HCEL - Electrical Underground  Partial Pass 9/25/24: okay to back fill trenches on east side of building for ev chargers, guard shack, pump house and sight lighting.
10/08/2024 COT - HCEL - Electrical Underground  Partial Pass X4 1” schedule 40 at 30” depth. 1 is for fire alarm and the three are for spares.
X1 1 1/4” remainder of tie in feeding electrical panel at fire house.
X1 1” for fiber pipe northwest of building for camera and light pole. Stubbed to server room. (IDF room) okay to backfill progress areas. 10/8/2024
10/20/2024 COT - HCEL - Electrical Underground  Partial Pass 2/7/24: partial for under ground electric
2/14/24: partial for under ground electric east of building okay to backfill trench
2/23/24: dock opening 1-4 okay to cover 3/4 conduit in wall
2/28/24: main electric room, east side of building column line 4 panel feeders okay to cover
3/7/24: main electric room electrical underground complete. Ok to backfill.

9/18/2024
Secondary feeders for Transformer 1 and 2. Cam locks for portable generators and permanent generator. Okay to backfill. Shading required. 9/18/2024
9/25/24: okay to back fill trenches on east side of building for ev chargers, guard shack, pump house and sight lighting.

X4 1” schedule 40 at 30” depth. 1 is for fire alarm and the three are for spares.
X1 1 1/4” remainder of tie in feeding electrical panel at fire house.
X1 1” for fiber pipe northwest of building for camera and light pole. Stubbed to server room. (IDF room) okay to backfill progress areas. 10/8/2024
10/18/24: Electrical underground for light pole bases at East side of project per plans. Pending inspection on light pole reinforcement and grounding. Ok to backfill progress area.
10/25/2024 COT - HCEL - Electrical Underground  Partial Pass 10/25/24: Electrical underground for light poles and gate controls on south side of project under main road is installed. Okay to shade conduit and backfill/compact trench.