Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCPL - Plumbing Final
Permit Number - TC-COM-0425-00797
Inspection Description - COT - HCPL - Plumbing Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2025 | COT - HCPL - Plumbing Final | Re-inspection required | 11-10-25: add R3 insulation to hot leg of water heater, lower all mirrors at restrooms to 40" to reflective surface, label junction boxes at warehouse side, missing ADA signs at restrooms (braile), missing electric over underneath sink at kitchen, warehouse bathroom fans not working, adjust min doors to 5 pounds of pressure. | |
| 11/24/2025 | COT - HCPL - Plumbing Final | Passed | 11-24-25: corrections made. Plumbing final approved. |