Permit: TC-COM-0226-00261

Parcel: 140410070


Addresses:

3430 E VALENCIA RD

Inspection Status: Partial Pass

Inspection History: COT - LCBU - Preslab  

Date Description Inspector Results Comments
09/24/2026 COT - LCBU - Preslab   Partial Pass 9/24/2026 Partial pass. Total of 44 spread footers. On grid lines B-E columns 2-12. Approved. Okay for concrete placement.
10/06/2026 COT - LCBU - Preslab   Passed 10/6/26: corrections made ok to proceed with concrete placement
10/06/2026 COT - LCBU - Preslab   Re-inspection required 10/6/26: pre slab it not ready- missing rebar at corners and reinforcement spacing for slab on grade at several areas is not per plans-add reinforcement where spacing is more than 18' o.c., provide a report together with photos with chairs every 4' o.c, a vapor barrier is required at areas having flooring. Reschedule inspection when ready.