Inspection Status: Partial Pass
Inspection History: COT - HCBU - Excavation/Rebar/Zoning
Permit Number - T22CM03955
Inspection Description - COT - HCBU - Excavation/Rebar/Zoning
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2025 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 11/1/24: reinforcement per plan at continuous footing at GL E/1-18, spread footings per plan at GL B-D/2-8 and B-D/10-17. Ok for concrete placement 11/7/24: Reinforcement per plans at Spread footers at GL A-E/9, continuous footer at GL A/1-18 and 18/A-E per plan ok to proceed. 11/20/24: reinforcement at slab per plan at pour 1 GL 9-13. 11/20/24: reinforcement at slab per plan at pour 3 ok to proceed. 12/3/24: Building 3C Pour 4 Slab on Grade rebar inspection passed. 12/9/24: building 3 pour 5 at slab on grade rebar inspection passed. 1/15/25: reinforcement per plan at panels 79-94, 1-10. Ok to proceed. |
|
| 01/21/2025 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 11/1/24: reinforcement per plan at continuous footing at GL E/1-18, spread footings per plan at GL B-D/2-8 and B-D/10-17. Ok for concrete placement 11/7/24: Reinforcement per plans at Spread footers at GL A-E/9, continuous footer at GL A/1-18 and 18/A-E per plan ok to proceed. 11/20/24: reinforcement at slab per plan at pour 1 GL 9-13. 11/20/24: reinforcement at slab per plan at pour 3 ok to proceed. 12/3/24: Building 3C Pour 4 Slab on Grade rebar inspection passed. 12/9/24: building 3 pour 5 at slab on grade rebar inspection passed. 1/15/25: reinforcement per plan at panels 79-94, 1-10. Ok to proceed. 1/21/25: reinforcement per plan at panels 34-5. Ok to proceed. |
|
| 01/29/2025 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 11/1/24: reinforcement per plan at continuous footing at GL E/1-18, spread footings per plan at GL B-D/2-8 and B-D/10-17. Ok for concrete placement 11/7/24: Reinforcement per plans at Spread footers at GL A-E/9, continuous footer at GL A/1-18 and 18/A-E per plan ok to proceed. 11/20/24: reinforcement at slab per plan at pour 1 GL 9-13. 11/20/24: reinforcement at slab per plan at pour 3 ok to proceed. 12/3/24: Building 3C Pour 4 Slab on Grade rebar inspection passed. 12/9/24: building 3 pour 5 at slab on grade rebar inspection passed. 1/15/25: reinforcement per plan at panels 79-94, 1-10. Ok to proceed. 1/21/25: reinforcement per plan at panels 34-5. Ok to proceed. 1/29/25: reinforcement per plan for pour 4. Ok to proceed with concrete placement. |
|
| 01/31/2025 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 11/1/24: reinforcement per plan at continuous footing at GL E/1-18, spread footings per plan at GL B-D/2-8 and B-D/10-17. Ok for concrete placement 11/7/24: Reinforcement per plans at Spread footers at GL A-E/9, continuous footer at GL A/1-18 and 18/A-E per plan ok to proceed. 11/20/24: reinforcement at slab per plan at pour 1 GL 9-13. 11/20/24: reinforcement at slab per plan at pour 3 ok to proceed. 12/3/24: Building 3C Pour 4 Slab on Grade rebar inspection passed. 12/9/24: building 3 pour 5 at slab on grade rebar inspection passed. 1/15/25: reinforcement per plan at panels 79-94, 1-10. Ok to proceed. 1/21/25: reinforcement per plan at panels 34-5. Ok to proceed. 1/29/25: reinforcement per plan for pour 4. Ok to proceed with concrete placement. 1/31/25: reinforcement per plans at fire pump room footing. |
|
| 02/14/2025 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 11/1/24: reinforcement per plan at continuous footing at GL E/1-18, spread footings per plan at GL B-D/2-8 and B-D/10-17. Ok for concrete placement 11/7/24: Reinforcement per plans at Spread footers at GL A-E/9, continuous footer at GL A/1-18 and 18/A-E per plan ok to proceed. 11/20/24: reinforcement at slab per plan at pour 1 GL 9-13. 11/20/24: reinforcement at slab per plan at pour 3 ok to proceed. 12/3/24: Building 3C Pour 4 Slab on Grade rebar inspection passed. 12/9/24: building 3 pour 5 at slab on grade rebar inspection passed. 1/15/25: reinforcement per plan at panels 79-94, 1-10. Ok to proceed. 1/21/25: reinforcement per plan at panels 34-5. Ok to proceed. 1/29/25: reinforcement per plan for pour 4. Ok to proceed with concrete placement. 1/31/25: reinforcement per plans at fire pump room footing. 2/14/25: reinforcement per plan at west end ramps for concrete setting pad footing for tilt up panels at ramps. |
|
| 02/21/2025 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 2-21-25, verified rebar tie for detail 103B on west end of building 3. | |
| 03/17/2025 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 11/1/24: reinforcement per plan at continuous footing at GL E/1-18, spread footings per plan at GL B-D/2-8 and B-D/10-17. Ok for concrete placement 11/7/24: Reinforcement per plans at Spread footers at GL A-E/9, continuous footer at GL A/1-18 and 18/A-E per plan ok to proceed. 11/20/24: reinforcement at slab per plan at pour 1 GL 9-13. 11/20/24: reinforcement at slab per plan at pour 3 ok to proceed. 12/3/24: Building 3C Pour 4 Slab on Grade rebar inspection passed. 12/9/24: building 3 pour 5 at slab on grade rebar inspection passed. 1/15/25: reinforcement per plan at panels 79-94, 1-10. Ok to proceed. 1/21/25: reinforcement per plan at panels 34-5. Ok to proceed. 1/29/25: reinforcement per plan for pour 4. Ok to proceed with concrete placement. 1/31/25: reinforcement per plans at fire pump room footing. 2/14/25: reinforcement per plan at west end ramps for concrete setting pad footing for tilt up panels at ramps. 2-21-25, verified rebar tie for detail 103B on west end of building 3. 3/17/25: reinforcement per plan at last ramp footing at south west corner of building 3 |
|
| 04/29/2025 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 4-29-25, reinforcement & vapor barrier per plans for pour back along the edges on east & northeast sections of Building 3. Okay to pour concrete. | |
| 05/06/2025 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 5-6-25, reinforcement for pour back on Building 3 approved. Okay to pour at progress areas. | |
| 10/29/2025 | COT - HCBU - Excavation/Rebar/Zoning | Passed | 10-29-25: previously inspected and approved. | |
| 11/01/2024 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 11/1/24: reinforcement per plan at continuous footing at GL E/1-18, spread footings per plan at GL B-D/2-8 and B-D/10-17. Ok for concrete placement | |
| 11/07/2024 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 11/1/24: reinforcement per plan at continuous footing at GL E/1-18, spread footings per plan at GL B-D/2-8 and B-D/10-17. Ok for concrete placement 11/7/24: Reinforcement per plans at Spread footers at GL A-E/9, continuous footer at GL A/1-18 and 18/A-E per plan ok to proceed. |
|
| 11/20/2024 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 11/1/24: reinforcement per plan at continuous footing at GL E/1-18, spread footings per plan at GL B-D/2-8 and B-D/10-17. Ok for concrete placement 11/7/24: Reinforcement per plans at Spread footers at GL A-E/9, continuous footer at GL A/1-18 and 18/A-E per plan ok to proceed. 11/20/24: reinforcement at slab per plan at pour 1 GL 9-13. |
|
| 11/26/2024 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 11/1/24: reinforcement per plan at continuous footing at GL E/1-18, spread footings per plan at GL B-D/2-8 and B-D/10-17. Ok for concrete placement 11/7/24: Reinforcement per plans at Spread footers at GL A-E/9, continuous footer at GL A/1-18 and 18/A-E per plan ok to proceed. 11/20/24: reinforcement at slab per plan at pour 1 GL 9-13. 11/20/24: reinforcement at slab per plan at pour 3 ok to proceed. |
|
| 12/03/2024 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 11/1/24: reinforcement per plan at continuous footing at GL E/1-18, spread footings per plan at GL B-D/2-8 and B-D/10-17. Ok for concrete placement 11/7/24: Reinforcement per plans at Spread footers at GL A-E/9, continuous footer at GL A/1-18 and 18/A-E per plan ok to proceed. 11/20/24: reinforcement at slab per plan at pour 1 GL 9-13. 11/20/24: reinforcement at slab per plan at pour 3 ok to proceed. 12/3/24: Building 3C Pour 4 Slab on Grade rebar inspection passed. |
|
| 12/09/2024 | COT - HCBU - Excavation/Rebar/Zoning | Partial Pass | 11/1/24: reinforcement per plan at continuous footing at GL E/1-18, spread footings per plan at GL B-D/2-8 and B-D/10-17. Ok for concrete placement 11/7/24: Reinforcement per plans at Spread footers at GL A-E/9, continuous footer at GL A/1-18 and 18/A-E per plan ok to proceed. 11/20/24: reinforcement at slab per plan at pour 1 GL 9-13. 11/20/24: reinforcement at slab per plan at pour 3 ok to proceed. 12/3/24: Building 3C Pour 4 Slab on Grade rebar inspection passed. 12/9/24: building 3 pour 5 at slab on grade rebar inspection passed. |