Permit: T21CM01719

Parcel: 11515214B

Inspection Status: Not Ready

Inspection History: COT - LCEL - Electrical Final 

Date Description Inspector Results Comments
10/27/2022 COT - LCEL - Electrical Final  Not Ready
11/02/2023 COT - LCEL - Electrical Final  Re-inspection required 11/2/23: wrong size breaker at condenser unit on roof should be 50A
Receptacle under sink and at water heater room not GFCI protected
Single 35A fuse needed at water heater
Missing hand dryers in restrooms and next to sink in office
Missing smokies in restrooms and art studio
11/29/2023 COT - LCEL - Electrical Final  Passed