| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2022 | COT - LCME - Mechanical Final | Not Ready | ||
| 05/25/2021 | COT - LCME - Mechanical Final | LBOWERS | Prior to Final Inspectn | Entered by LBOWERS1 - AIR BALANCE REPORT REQUIRED |
| 11/02/2023 | COT - LCME - Mechanical Final | Re-inspection required | 11/2/23: wrong size breaker at condenser unit on roof should be 50A Receptacle under sink and at water heater room not GFCI protected Single 35A fuse needed at water heater Missing hand dryers in restrooms and next to sink in office Missing smokies in restrooms and art studio |
|
| 11/29/2023 | COT - LCME - Mechanical Final | Passed |