Permit: T19CM07159

Parcel: 11504475B


Addresses:

1055 N PARK AV

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
11/09/2021 FIRE - FINAL Approved Need signage:
"Combo" and inlet pressure at FDC
Riser labels in pump room
08/12/2021 FIRE - FINAL Partial Approval OK to obtain TCO from building department.

Items needed for C of O

Stair 3, floor 3 door sticking
-Stair 1, LL and floor 1 doors sticking
-Stair 1, gate is blocking access to the standpipe connection. We need to be able to access that and run a hose up the stairs
-Verify that stair illumination stripping is complete
-Placard indicating the FDC inlet pressure at the FDC
-Elevator 2 way communication needs to be tested
The DBA for ERRC (Emergency Responder Radio Coverage) needs to be installed and tested.
- Add 2 sets of keys to the knox box at command center.
-Install labels on sprinkler components in pump room.