Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2021 | FIRE - FINAL | Approved | ||
| 10/28/2020 | FIRE - FINAL | Partial Approval | Permanent signs on electrical rooms Interior standpipes labeled 2" letters Keys in Knoxbox by main entrance. (Aready in other two) Verify EM responder radio coverage Verify Knox key opens Northwest gate APPROVED TO OBTAIN TCO |
|
| 10/27/2020 | FIRE - FINAL | Partial Approval | Standpipe signage Keys in Knoxbox Electrical room signs Verify main entrance egress Verify UL labels visible on rated doors. FACP signage Verify EM responder radio coverage |