Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/10/2020 |
FIRE SPKLR - FINAL |
|
Approved |
|
| 05/14/2019 |
FIRE SPKLR - FINAL |
|
Partial Approval |
Tested the fire pump with the fire alarm system. Confirmed, phase reversal, power loss and pump running with the fire alarm system and offsite fire alarm monitoring. Tested all the fire sprinkler water flow and tamper swicthes B's-9 and confirmed signals to the FACP and the monitoring. Need to test the fire pump with the emergency power on June 26th at 8:30 am. |