Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T18CM00946

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/16/2019 MECHANICAL - INTERMEDIATE Approved
06/28/2019 MECHANICAL - INTERMEDIATE Not ready for Inspection Cancel by contractor
06/14/2019 MECHANICAL - INTERMEDIATE Partial Approval Fire damper, room #313.
06/13/2019 MECHANICAL - INTERMEDIATE Partial Approval Yoga room Is ready for sheet rock. Computer room second layer of sheet rock, however missing fire caulk.
06/12/2019 MECHANICAL - INTERMEDIATE Partial Approval Fifth floor public restroom.
06/11/2019 MECHANICAL - INTERMEDIATE Cancelled Canceled by contractor
06/10/2019 MECHANICAL - INTERMEDIATE Partial Approval Fire dampers 401,402, 403, 404, 405, 406, 407, 411, 413, 203.
06/10/2019 MECHANICAL - INTERMEDIATE Partial Approval 5th floor restrooms
06/07/2019 MECHANICAL - INTERMEDIATE Partial Approval Unit number 201, 212, 211, 218, 410, 409, 408
06/06/2019 MECHANICAL - INTERMEDIATE Partial Approval fire dampers in units 202, 204, 205.
06/04/2019 MECHANICAL - INTERMEDIATE Partial Approval
06/03/2019 MECHANICAL - INTERMEDIATE Partial Approval Level #3, 8 Room Fire dampers secured. Ok to cover progress areas.
05/22/2019 MECHANICAL - INTERMEDIATE Partial Approval Yoga/Fitness areas; Main entry. (above ceiling). Ensure all penetrations are fire caulked.
05/21/2019 MECHANICAL - INTERMEDIATE Not ready for Inspection Contractor cancelled.
05/20/2019 MECHANICAL - INTERMEDIATE Cancelled no work to inspect at this time
05/16/2019 MECHANICAL - INTERMEDIATE Partial Approval Fire dampers. Units number 209, 217, 216, 214, 303, 304, 305, 306, 307, 308, 418, 417, 414, 415, 416.
05/15/2019 MECHANICAL - INTERMEDIATE Not ready for Inspection not complete
05/13/2019 MECHANICAL - INTERMEDIATE Partial Approval Unit number 417 OK
Unit number 416, dryer vent has too many bends, support dampers on three sides, seal off firewall. Unit number 418, support triple trusses, missing nails in triple trust hangers.
05/10/2019 MECHANICAL - INTERMEDIATE Partial Approval third-floor Corridor
05/09/2019 MECHANICAL - INTERMEDIATE Partial Approval Unit number 414
05/08/2019 MECHANICAL - INTERMEDIATE Partial Approval Unit number 415
05/07/2019 MECHANICAL - INTERMEDIATE Not ready for Inspection not complete
05/06/2019 MECHANICAL - INTERMEDIATE Partial Approval townhouse unit number 111 and corridor on the second floor
05/03/2019 MECHANICAL - INTERMEDIATE Partial Approval Level #1, Room #110. Ok to insulate and Sheetrock progress areas.
05/01/2019 MECHANICAL - INTERMEDIATE Not ready for Inspection
04/30/2019 MECHANICAL - INTERMEDIATE Partial Approval Units number 411 and townhouse number 112.
04/29/2019 MECHANICAL - INTERMEDIATE Not ready for Inspection Not completed enough
04/26/2019 MECHANICAL - INTERMEDIATE Partial Approval Units number 412 and 413
04/25/2019 MECHANICAL - INTERMEDIATE Partial Approval Unit number 413 secured 3 inch pipes, support roof drains, missing fire caulk in firewall, Missing smoke detector boxes,
04/24/2019 MECHANICAL - INTERMEDIATE Partial Approval unit number 403. Unit 401 has cut trusses above the north window, hole in firewall, clamps missing on plumbing pipes. Stop Inspection
04/22/2019 MECHANICAL - INTERMEDIATE Partial Approval Units number 404, 405 and 406.
Unit 403 frame shower out to 2 x 6 not 2 x 4, unit 402 exhaust fan termination cut in half at termination.
04/19/2019 MECHANICAL - INTERMEDIATE Partial Approval Unit number 406 has plumbing lines feeding unit number. Seal off holes in top plate in mechanical room,405 to the kitchen and refrigerator. Unit 406 seal off holes in the top plate at mechanical room.
Unit number 405 missing clamps on plumbing pipes on south wall, filling holes in firewall, install fire stop in mechanical room.
04/18/2019 MECHANICAL - INTERMEDIATE Partial Approval Units number 406, 407 and 408.
Townhouse unit number 112. Back bitch on 3 inch double toilet pipe in east bedroom. 3 inch support missing in south bedroom. There is a 3 inch pipe in the stairwell ceiling, no one knows where it goes.
Townhouse number 111 missing steel studs, relocate smoke detector in bedroom, secure studs on second-floor firewall, resecure water supply. Stop inspection
04/17/2019 MECHANICAL - INTERMEDIATE Partial Approval Units number 408, 409, and 410
04/16/2019 MECHANICAL - INTERMEDIATE Not ready for Inspection unit not complete
04/15/2019 MECHANICAL - INTERMEDIATE Partial Approval unit 410 only
04/12/2019 MECHANICAL - INTERMEDIATE Partial Approval Unit number 314, 316, and 317
04/11/2019 MECHANICAL - INTERMEDIATE Partial Approval Unit Number 315
04/09/2019 MECHANICAL - INTERMEDIATE Partial Approval Units number 301, 312, 313
04/08/2019 MECHANICAL - INTERMEDIATE Partial Approval Unit number 211
04/05/2019 MECHANICAL - INTERMEDIATE Partial Approval Units number 305, 304, 303 and 302
04/04/2019 MECHANICAL - INTERMEDIATE Partial Approval Third-floor unit 309 and 310. Units number 307 and 308 require detail for fire damper in the mechanical room
04/02/2019 MECHANICAL - INTERMEDIATE Partial Approval Townhouse units. Flex duck needs to be rerouted
04/01/2019 MECHANICAL - INTERMEDIATE Cancelled canceled by contractor
03/28/2019 MECHANICAL - INTERMEDIATE Partial Approval Units number 215, 217, 218
03/28/2019 MECHANICAL - INTERMEDIATE Partial Approval Units number 215, 217, 218.
03/27/2019 MECHANICAL - INTERMEDIATE Cancelled Cancel by contractor
03/26/2019 MECHANICAL - INTERMEDIATE Not ready for Inspection Not complete enough
03/25/2019 MECHANICAL - INTERMEDIATE Cancelled canceled by the contractor.
03/21/2019 MECHANICAL - INTERMEDIATE Denied Unit number 213. Missing Firefox, missing plumbing supports, sheet rock screws it hat channel, steel post missing supports, missing fire damper assembly.
Units number to 12 and 211 not ready. Not complete enough
03/20/2019 MECHANICAL - INTERMEDIATE Partial Approval Units number 215 and 214
03/18/2019 MECHANICAL - INTERMEDIATE Partial Approval Room number 215
03/15/2019 MECHANICAL - INTERMEDIATE Not ready for Inspection not complete
03/13/2019 MECHANICAL - INTERMEDIATE Partial Approval For unit 202,203 and 204
03/11/2019 MECHANICAL - INTERMEDIATE Partial Approval For unit 202, 203, 204 fire caulk all exterior penetrations, all line sets in washer and dryer vents. Land all wires in the panel box.
03/08/2019 MECHANICAL - INTERMEDIATE Not ready for Inspection not complete enough
03/07/2019 MECHANICAL - INTERMEDIATE Partial Approval Unit number 205
03/06/2019 MECHANICAL - INTERMEDIATE Partial Approval For unit 206, 207 and 208
03/05/2019 MECHANICAL - INTERMEDIATE Partial Approval Unit number 209 is complete,
Unit number 208 secure all flex duct install dryer duct secure plumbing distribution pipe and DWV’s.
03/01/2019 MECHANICAL - INTERMEDIATE Not ready for Inspection Not complete enough
02/14/2019 MECHANICAL - INTERMEDIATE Not ready for Inspection Not complete enough