Permit: T18CM00946

Parcel: 11504498B


Addresses:

850 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T18CM00946

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
07/31/2019 EXT METAL CLIPS/EXT SHEATHING Approved
05/13/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Unit number 417 OK
Unit number 416, dryer vent has too many bends, support dampers on three sides, seal off firewall. Unit number 418, support triple trusses, missing nails in triple trust hangers.
05/10/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval third-floor Corridor
05/09/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval
05/08/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Unit number 415
05/07/2019 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection not complete
05/06/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval townhouse unit number 111 and corridor on the second floor
05/03/2019 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection Contractor cancelled.
05/01/2019 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection
04/30/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Units number 411 and townhouse number 112.
04/29/2019 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection Not completed enough
04/26/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Units number 412 and 413
04/25/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Unit number 413 secured 3 inch pipes, support roof drains, missing fire caulk in firewall, Missing smoke detector boxes,
04/24/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval unit number 403. Unit 401 has cut trusses above the north window, hole in firewall, clamps missing on plumbing pipes. Stop Inspection
04/22/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Units number 404, 405 and 406.
Unit 403 frame shower out to 2 x 6 not 2 x 4, unit 402 exhaust fan termination cut in half at termination.
04/19/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Unit number 406 has plumbing lines feeding unit number. Seal off holes in top plate in mechanical room,405 to the kitchen and refrigerator. Unit 406 seal off holes in the top plate at mechanical room.
Unit number 405 missing clamps on plumbing pipes on south wall, filling holes in firewall, install fire stop in mechanical room.
04/18/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Units number 406, 407 and 408.
Townhouse unit number 112. Back bitch on 3 inch double toilet pipe in east bedroom. 3 inch support missing in south bedroom. There is a 3 inch pipe in the stairwell ceiling, no one knows where it goes.
Townhouse number 111 missing steel studs, relocate smoke detector in bedroom, secure studs on second-floor firewall, resecure water supply. Stop inspection
04/17/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Units number 408, 409, and 410
04/16/2019 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection unit not complete
04/15/2019 EXT METAL CLIPS/EXT SHEATHING Cancelled Already covered with waterproofing. Per Antonio, this has been checked by hitting from inside. Super will wait for return of Ernie, as he has checked during work progress.
04/12/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Unit number 314, 316, and 317
04/11/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Unit Number 315
04/09/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Units number 301, 312, 313
04/08/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Unit number 211
Westside exterior wall on the 3rd floor
04/05/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Units number 305, 304, 303 and 302
04/04/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Third-floor unit 309 and 310. Units number 307 and 308 require detail for fire damper in the mechanical room
04/02/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Townhouse units. Not all stud screwed to sole plate.
04/01/2019 EXT METAL CLIPS/EXT SHEATHING Cancelled canceled by contractor
03/28/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Units number 215, 217, 218
03/28/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Units number 215, 217, 218.
03/27/2019 EXT METAL CLIPS/EXT SHEATHING Cancelled Cancel by contractor
03/26/2019 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection Not complete enough
03/25/2019 EXT METAL CLIPS/EXT SHEATHING Cancelled canceled by the contractor.
03/21/2019 EXT METAL CLIPS/EXT SHEATHING Denied Unit number 213. Missing Firefox, missing plumbing supports, sheet rock screws it hat channel, steel post missing supports, missing fire damper assembly.
Units number to 12 and 211 not ready. Not complete enough
03/20/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval North exterior shear wall on 4th floor. Also units 215 and 214
03/18/2019 EXT METAL CLIPS/EXT SHEATHING Denied Unit 215 is not approved. Missing bolts in glue Lam in bathroom header, also missing nails in Joyce hangers. Missing anchor bolts on sheer wall. Not all nuts are tight on anchor bolts
03/15/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval northside sheer walls and anchor bolts only line one from B to G second and third floor.
03/13/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Unit 212 and 213 complete; unit 201, tighten bolts on ledger board, repair holes in floor, repair over bored holes in 2x’s , seal off dead spaces.
03/11/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Line 1 columns G through J floors 23 and four. This is the north east corner.
03/08/2019 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection not complete enough
03/07/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Unit 203 and 202
03/06/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval For unit 206, 207 and 208
03/06/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Four units 204 and 205; also on east wall of townhouse installed dens glass
03/05/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Unit 206 missing pins in sole plate, missing nuts on anchor bolts at washer dryer area, north wall and Southwall;
Unit number 210, missing hole down, missing lag bolts in 4 x 4 steel, missing lag bolts on glue Lam saddle in courtyard
Unit number 207,208, 209 are complete.
02/25/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Fourth floor, line 7 columnG through J. Rose one through seven column J.
02/22/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Second-floor east side exterior wall. Third floor east wall and south east corner
02/20/2019 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection Not complete enough
02/12/2019 EXT METAL CLIPS/EXT SHEATHING Cancelled canceled by contractor
01/29/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Level two all exterior walls OK to cover
01/25/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval East side units number 202 through 204, courtyard exterior and interior shear walls. Also exterior south side walls
01/23/2019 EXT METAL CLIPS/EXT SHEATHING Partial Approval Units number 205 through 210, courtyard exterior and interior shear walls only.
01/11/2019 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection Not complete enough.