Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2019 | FIRE - ALARM FINAL | Approved | ||
| 03/04/2019 | FIRE - ALARM FINAL | Denied | Central alarm is recieving signals to the central staion but permit was never closed out, smoke detector is hanging on the wall, security siren goes off on alarm and either needs to be removed and or meet the NFPA 72 signaling requirements. Panel is located in a mop closet, need to verify with Central Alarm that the panel is listed for use in a wet area. | |
| 03/01/2019 | FIRE - ALARM FINAL | Denied | nobody on site. no message. alarm permit not called in. alarm plans not on site. alarm contractor not on site. |
|
| 02/25/2019 | FIRE - ALARM FINAL | Denied | 1. Need to upgrade Fire Sprinkler Monitoring. |