Permit: T17CM00366

Parcel: 11720015A


Addresses:

111 S CHURCH AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T17CM00366

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/18/2018 FIRE - FINAL Approved Completed
12/13/2018 FIRE - FINAL Partial Approval Tested everything with the fire alarm and fire sprinkler system. Need to add labels to the two way communication, take down barricades, finish paint, add elevator lobby lights for full CofO. Ok for TCO 4-7 JMPD
12/04/2018 FIRE - FINAL Partial Approval Tested the fire sprinkler systems on the 4-7th floor for proper operation.
Ok for TCO
They still need to test the fire alarm 4-7, emergency and exit lights 4-7 and two-way communication.
7th floor waterflow 31 seconds
6th floor waterflow 31 seconds
5th floor waterflow 33 seconds
4th floor waterflow 32 seconds
12/03/2018 FIRE - FINAL Cancelled Contractor called to say that they were not ready
11/30/2018 FIRE - FINAL Cancelled IVRS - RI canceled
11/15/2018 FIRE - FINAL Partial Approval Tested the notification devices on the 1st, 2nd and 3rd floors. Tested the fire sprinkler flows:North Stairwell 41 seconds1st floor 25 secondsSouth Stairwell 34 seconds2nd floor 35 seconds3rd floor 32 seconds. Tested all control valves located on the 1st, 2nd and third floors. Confirmed the monitoring signals off site

Checked every room located on the 1st, 2nd and 3rd floor for the fire sprinkler final. Fire sprinkler approved for these three floors.
Fire pump to be left operational once the two heads under the stairs are added

Electrical engineer to provide the photometric data for the emergency lights located in the north corridor
2nd floor ne exit sign is not working
3rd floor ne 2 exit signs are not working properly
Room 203 bedroom smoke detector need to be replaced
Room 310 hall smoke detector needs to be replaced
Need to order the KNOX FDC Caps
Need to order a F.A.C.P. Sign
Need to have address posted on the Broadway side to read: 111 S. Church
Keys placed in the KNOX Boxes
Building requires two-way communication at the elevators
One elevator still needs to be commissioned by the State Elevator Inspector
Glenn D'Auria made arrangements with them regarding building separation and a TCO. It is up to Glenn D'Auria to see if they have met the expectations for separation that he set with them. I will not approved for TCO. TCO pending approval from Glenn D'Auria and or Michael Ashford on behalf of TFD.