Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/08/2017 |
FIRE - ALARM FINAL |
|
Approved |
To site w/Simplex. Test ok |
| 05/05/2017 |
FIRE - ALARM FINAL |
|
Partial Approval |
Flow 37 seconds, smoke detector ok, manual pull ok, tamper and water flow ok. Need to add a visual in the office. Need to verify ambient sound. Need to verify monitoring. |