Permit: T10CM00917

Parcel: 12620001C


Addresses:

3400 E ZOO CT


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T10CM00917

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/23/2012 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
10/27/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DRAIN WASTE AND VENT LSS OK EXCEPT FOR 2-4" P-TRAPS WITH VENTING FOR ABOVE SLAB
08/22/2011 PLUMBING - INTERMEDIATE Not ready for Inspection WATER TEST ONLY FOR VENTS IN BLOCK WALL OF LSS BUILDING. PROVIDE AN ISOMETRIC DETAIL OF DRAINAGE IN LSS (2) 4" HUB DRAINS ARE SHOWN CURRENTLY NO P-TRAPS, AND HUB DRAINS DO NOT MEET 2006 UPC REQUIREMENTS. PROVIDE SPEC INSTALL OF HANGING & SUPPORTS FOR OVERHEAD DRAINAGE IN LSS TANK OR STAMPED LETTER FROM ENGINEER FOR SUBSTITUTE
08/16/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/15/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) WRAP VENT PIPING IN SOLID GROUTED BLOCK CELLS AND PROVIDE TEST ON ALL PIPING
06/21/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*