Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T10CM00917
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2012 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/27/2011 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DRAIN WASTE AND VENT LSS OK EXCEPT FOR 2-4" P-TRAPS WITH VENTING FOR ABOVE SLAB |
|
08/22/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | WATER TEST ONLY FOR VENTS IN BLOCK WALL OF LSS BUILDING. PROVIDE AN ISOMETRIC DETAIL OF DRAINAGE IN LSS (2) 4" HUB DRAINS ARE SHOWN CURRENTLY NO P-TRAPS, AND HUB DRAINS DO NOT MEET 2006 UPC REQUIREMENTS. PROVIDE SPEC INSTALL OF HANGING & SUPPORTS FOR OVERHEAD DRAINAGE IN LSS TANK OR STAMPED LETTER FROM ENGINEER FOR SUBSTITUTE | |
08/16/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
08/15/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) WRAP VENT PIPING IN SOLID GROUTED BLOCK CELLS AND PROVIDE TEST ON ALL PIPING |
|
06/21/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |