Case: T09FR03335

Parcel: 11449042P


Addresses:

2422 N PANTANO RD

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
03/01/2010 VIOL - FIRE PROTECTION SYSTEMS Approved All approved - good job / closed
10/21/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishers not tagged / inspected:

TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code.
10/21/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Hood system:
904.11 Commercial cooking systems. The automatic fire-extinguishing system for commercial cooking systems shall be of a type recognized for protection of commercial cooking equipment and exhaust systems of the type and arrangement protected. Preengineered automatic dry- and wet-chemical
extinguishing systems shall be tested in accordance with UL 300 and listed and labeled for the intended application. Other types of automatic fire-extinguishing systems shall be listed and labeled for specific use as protection for commercial cooking operations. The system shall be installed in accordance with this code, its listing and the manufacturer's installation instructions. Automatic fire-extinguishing systems of the following types shall be installed in accordance with the referenced standard indicated, as follows:
1. Carbon dioxide extinguishing systems, NFPA 12.
2. Automatic sprinkler systems, NFPA 13.
3. Foam-water sprinkler system or foam-water spray systems,
NFPA 16.
4. Dry-chemical extinguishing systems, NFPA 17.

_______ Supply a report ensuring compliance with the above directive. [UL 300 system]
10/21/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Filthy Hood, Screens and Plenum:
904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall
state the extent, time and date of cleaning. Such records shall be maintained on the premises.
********************************************************************
______ This is extremely important as this buildup is FLAMMABLE- Clean this regularly so at no time is it this greasy. Periodic checks will be done to make sure of compliance. You have been written up for this problem before.
+++++++++++++++++++++++++++++++++++++++++++++++++++++
10/21/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Smoke alarm - in disrepair:

TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

______ Systems [smoke / alarm] shall be maintained, inspected and tagged [annually] in accordance with this code. Provide proof of same to the fire marshal.

Re-inspection date scheduled on or after November 9th, 2009.
If you have any questions or concerns please call Inspector Cobb at 837-7106.
Thank you,

_____________________________________________
Brian Cobb, Inspector, Tucson Fire Department


__________________________ - I have received a copy of this inspection report.
Building Representative


Re-inspection approved: ___________________________Date:__________


Captain - Tucson Fire Dept. ________________________________________