Description:

Full inspection done 10/21/09; Jack Kenney 885-6585; A-2 occupancy [C of O 182 persons]

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03335
Case Description: INSPECTION
Total Completed Inspections - 15
End Date Description Inspector Results Comments
10/21/2009 VIOL - FIRE PROTECTION SYSTEMS BCOBB Approved Smoke alarm - in disrepair: TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ Systems [smoke / alarm] shall be maintained, inspected and tagged [annually] in accordance with this code. Provide proof of same to the fire marshal. Re-inspection date scheduled on or after November 9th, 2009. If you have any questions or concerns please call Inspector Cobb at 837-7106. Thank you, _____________________________________________ Brian Cobb, Inspector, Tucson Fire Department __________________________ - I have received a copy of this inspection report. Building Representative Re-inspection approved: ___________________________Date:__________ Captain - Tucson Fire Dept. ________________________________________
10/21/2009 VIOL - FIRE PROTECTION SYSTEMS BCOBB Approved Filthy Hood, Screens and Plenum: 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. ******************************************************************** ______ This is extremely important as this buildup is FLAMMABLE- Clean this regularly so at no time is it this greasy. Periodic checks will be done to make sure of compliance. You have been written up for this problem before. +++++++++++++++++++++++++++++++++++++++++++++++++++++
10/21/2009 VIOL - FIRE PROTECTION SYSTEMS BCOBB Approved Hood system: 904.11 Commercial cooking systems. The automatic fire-extinguishing system for commercial cooking systems shall be of a type recognized for protection of commercial cooking equipment and exhaust systems of the type and arrangement protected. Preengineered automatic dry- and wet-chemical extinguishing systems shall be tested in accordance with UL 300 and listed and labeled for the intended application. Other types of automatic fire-extinguishing systems shall be listed and labeled for specific use as protection for commercial cooking operations. The system shall be installed in accordance with this code, its listing and the manufacturer's installation instructions. Automatic fire-extinguishing systems of the following types shall be installed in accordance with the referenced standard indicated, as follows: 1. Carbon dioxide extinguishing systems, NFPA 12. 2. Automatic sprinkler systems, NFPA 13. 3. Foam-water sprinkler system or foam-water spray systems, NFPA 16. 4. Dry-chemical extinguishing systems, NFPA 17. _______ Supply a report ensuring compliance with the above directive. [UL 300 system]
10/21/2009 VIOL - FIRE PROTECTION SYSTEMS BCOBB Approved Extinguishers not tagged / inspected: TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code.
10/21/2009 VIOL - FIRE RESIST.RATED CONST BCOBB Approved Missing, Damaged or Moved ceiling tiles: TFC2006/ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. _____Replace missing or damaged ceiling tiles. [everywhere- DR and Kit]
10/21/2009 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Wires bad on light signal system for servers: TFC2006/ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ______ Replace wires in an approved manor. [and check all other equipment for electrical hazards] No tape allowed.
10/21/2009 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Open wire boxes/ splices/ hazards: TFC2006 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ______Cover wires in an approved manner. [outlet behind juke box and burned outlet behind big TV in DR -replace outlet.] _____ Fix outside electrical conduit hanging by the patio. _____ Show proof from a licenced electrician [with Lic #] that the electrical lights over pool tables are wired in conpliance with the Electrical Code or have them removed and capped or wired legally.
10/21/2009 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Extension cords: TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove or replace with approved fused power strip. [TV behind bar and behind Juke Box]
10/21/2009 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Electrical wires extending through ceiling: TFC2006/ 605.5 Flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors. ______ Please remove wires. Multiple locations. Power supply in pool rm, pinched wires in ceiling tile, DR TV and signs...
10/21/2009 VIOL - MEANS OF EGRESS BCOBB Approved Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights.
10/21/2009 VIOL - MEANS OF EGRESS BCOBB Approved Exit signs: TFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. ______Place exit signs in an approved manner on the patio gate- Red letters on White background; 3" minimum.
10/21/2009 VIOL - MEANS OF EGRESS BCOBB Approved Bolt lock: TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ______Remove bolt lock.
10/21/2009 VIOL - MEANS OF EGRESS BCOBB Approved Bars on doors: 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _______Remove bar and all associated hardware from doors. [2 dining room doors] All hardware to be taken from premises. Notes: FYI-Panic Hardware: TFC2006 / 1028.8 [Tucson Fire Code Modifications] Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.
10/21/2009 VIOL - PRECAUTION AGAINST FIRE BCOBB Approved Housekeeping: Heater, Stove, Hood, Floors etc. TFC 304.1 Waste accumulation prohibited. Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. _____ Clean around water heater, floors, stoves, and general kitchen and back area. I will refer to County Health Department if I feel this is still unsatisfactory at the time of the final Fire inspection.
10/21/2009 INSP - FULL BCOBB Approved Please correct the following Tucson Fire Code violations: Notes: 1. A record of the Hood system inspections shall be made available upon re-inspection. Any deficiencies must be corrected.