Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2010 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
| 10/21/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Electrical wires extending through ceiling: TFC2006/ 605.5 Flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors. ______ Please remove wires. Multiple locations. Power supply in pool rm, pinched wires in ceiling tile, DR TV and signs... |
|
| 10/21/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Extension cords: TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove or replace with approved fused power strip. [TV behind bar and behind Juke Box] |
|
| 10/21/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Open wire boxes/ splices/ hazards: TFC2006 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ______Cover wires in an approved manner. [outlet behind juke box and burned outlet behind big TV in DR -replace outlet.] _____ Fix outside electrical conduit hanging by the patio. _____ Show proof from a licenced electrician [with Lic #] that the electrical lights over pool tables are wired in conpliance with the Electrical Code or have them removed and capped or wired legally. |
|
| 10/21/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Wires bad on light signal system for servers: TFC2006/ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ______ Replace wires in an approved manor. [and check all other equipment for electrical hazards] No tape allowed. |