Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2010 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* 1) RECEIVED LETTER OF TORQUE AND GFI TEST |
|
| 06/30/2010 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) SERVICE SECONDARYS ALREADY INSTALLED 2) MUST USE BONDING FITTINGS RATED FOR BONDING AT SERVICES PER 250-92 NEC. AHEAD OF OVERCURRENT PROTECTION. STANDARD LOCKNUTS, P-BUSHINGS NOT APPROVED 3) HUBS MUST BE LISTED FOR BONDING AT SERVICES |