Permit: T09CM02372

Parcel: 21116006A

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
07/02/2010 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
1) RECEIVED LETTER OF TORQUE AND GFI TEST
06/30/2010 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1) SERVICE SECONDARYS ALREADY INSTALLED
2) MUST USE BONDING FITTINGS RATED FOR BONDING AT SERVICES PER 250-92 NEC. AHEAD OF OVERCURRENT PROTECTION. STANDARD LOCKNUTS, P-BUSHINGS NOT APPROVED
3) HUBS MUST BE LISTED FOR BONDING AT SERVICES