Permit: T09CM01449

Parcel: 12709011P

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM01449

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/05/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/03/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED A/C DISCONNECT GROUND BAR BONDED
2) NEED PROPER SIZE WIRE TO FEED DISCONNECT A/C
3) NEED OUTLET CIRCUITS TO BE TO PRINT
07/30/2009 ELECTRIC - FINAL Denied PANEL SCHEDULE NEEDS TO BE REVISED
PRINT NEEDS TO BE CHECKED FOR LIGHTING CIRCUIT
NEED LADDER TO SEE ROOF AC
NEED WATER HEATER DISCONNECT LABELED
NEED TO SEE WHAT TYPE OF DISCONNECT NEEDED FOR WATER HEATER & AC