Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 03/04/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) NEED PERMANENT PANEL DIRECTORIES PER 408.4 2) FILL UNUSED OPENINGS 3) PANEL LABELING TO BE PER 210.5 (C) 4) FINISH VDV |
|
| 02/19/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 01/11/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 11/06/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 11/05/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/18/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/17/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/15/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPORT POWER POLES 2) FINISH VDV RUNS FOR POWER POLES 3) SUPPORT M/C WITHIN 12" OF BOX 4) VERIFY DERATING PER 310.15 5) HANDLE TIES PER 605.7 6) BOND FLOOR BOX ENCLOSURE 250.148 7) SUPPORT FLEX CONDUIT OVER 4' AS PER CODE 8) FINISH 1, 2 & 3 OF PREVIOUS |
|
| 09/01/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/10/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/07/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/22/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |