Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM01053
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/18/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/19/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH VDV CABLING 2) CORDS NOT ALLOWED ABOVE CELING-INSTALL LIGHTINT PER INSTRUCTIONS 3) PROTECT CONDUCTORS 300.4 4) SUPPORT M/C AND FLEX PER CODES 5) SECURELY ATTACH FIXTURES TO GRID 410.16 |
|
01/11/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) TEMP LIGHTING POWER TO BE MADE SAFE |
|
10/27/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK SURFACE MOUNTED RACEWAYS ON WALL PHASE II 2) OK TO CABLE TRAY BOND TO BLDG STEEL |
|
09/01/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ATTACH CEILING WIRES PER 300.11 AND INDEPENDENT 2) FINISH VDV CABLING 3) SECURE UPON EXIT FO CABLE TRAY 392 4) PROTECT ENDS OF RACEWAY FOR VDV CABLING 5) FINISH POWER POLES 6) OK BOND FOR BOND RAIL 7) OK TILE AS DISCUSSED SUBJECT TO OTHER TRADES |
|
08/10/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ROOMS PHASE I WALLS AND CONDUIT ON CEILING 2) OK CABLE TRAY BONDING AND CONDUIT ATTACHMENTS |
|
08/07/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) WILL RESCHEDULE |
|
07/22/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SUPPORT CONDUIT 3' + 10' 2) FILL UNUSED OPENINGS IN BOXES 3) FINISH VDV CONDUIT RUNS 4) BONDING FOR CABLE TRAY PER 392 5) NO MORE THAN 360 DEGREE IN A RUN |