Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
Permit Number - T09BU00652
Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/21/2009 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | TESTED AT 250PSI FOR 2HOURS | |
05/18/2009 | FIRE SPKLR - UG, PIPING, HYDRO | Denied | THRUST BLOCKING ON 45'S GAVE WAY CAUSING PIPING TO COME APART. NEED TO POUR BIGGER THRUST BLOCKING UP AGAINST HARD GROUND AND NOT SAND SO BLOCKING DOES NOT MOVE OR USE RESTRAINTS ON ALL BELL CONNECTIONS. |