Permit: T09BU00652

Parcel: 14122004L


Addresses:

8755 S RITA RD


Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Permit Number - T09BU00652

Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
05/21/2009 FIRE SPKLR - UG, PIPING, HYDRO Approved TESTED AT 250PSI FOR 2HOURS
05/18/2009 FIRE SPKLR - UG, PIPING, HYDRO Denied THRUST BLOCKING ON 45'S GAVE WAY CAUSING PIPING TO COME APART. NEED TO POUR BIGGER THRUST BLOCKING UP AGAINST HARD GROUND AND NOT SAND SO BLOCKING DOES NOT MOVE OR USE RESTRAINTS ON ALL BELL CONNECTIONS.