Case: T08FR04187

Parcel: 12404098A


Addresses:

947 N PARK AV


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T08FR04187

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/01/2009 INSP - FULL Correction Required THIS OFFICE RECEIVED A COPY OF THE CORRECTION REPORT FROM THE SPRINKLER CONTRACTOR. THERE IS STILL THE FOLLOWING DEFICIENCY THAT SHALL BE ADRESSED WITH IN 30 DAYS. UNTIL COMPLETION THE PRE-CITATION WILL REMAIN IN FORCE. ATTACHED IS A PARTIAL COPY OF THEIR REPORT.

1) THE ALARM VALVE CLAPPER IS NOT SEATING TIGHTLY.
04/10/2009 INSP - FULL Correction Required PRECITATION SENT 4-8-09
02/13/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 11-5-08, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT
947 N. PARK. IF CORRECTED, HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
11/05/2008 INSP - FULL Correction Required DURING THE ANNUAL FIRE SPRINKLER INSPECTION, FEB.,5,2008, THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE

1) SPRINKLERS THAT ARE 50 YEARS OLD SHALL HAVE A SAMPLE TESTED OR SHALL BE REPLACED AS PER NATIONAL FIRE PROTECTION STANDARDS.

2) THE ALARM CLAPPER VALVE IS NOT SEATING CORRECTLY AND THE ALARM BELL RINGS INTERMITTANTLY. IT SHALL BE REPAIRED OR REPLACED IF NECESSARY

3) MISSING CEILING TILES SHALL BE REPLACED