Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR01238
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/03/2008 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.06/03/08 | |
05/15/2008 | INSP - FULL | Violation | 1.) TFC 1003.6 BAND EQUIPMENT BLOCKING EMERGENCY EXIT. THIS DOOR MSUT BE UNBLOCKED AT ALL TIMES. | |
05/15/2008 | INSP - FULL | Violation | 2.) TFC 1008.1.9 WHERE PANIC EXIT HARDWARE EXISTS NO OTHER LOCKS ARE ALLOWED TO BE USED ON THE DOOR. KEYED LOCK MSUT BE REMOVED. | |
05/15/2008 | INSP - FULL | Violation | 3.) TFC 605.4 MULTI-PLUG CUBE ADAPTORS IN NUMEROUS LOCATIONS ON INSIDE OF EXTERIOR WALLS ARE NOT ALLOWED TO BE USED. | |
05/15/2008 | INSP - FULL | Violation | 4.) TFC 605.5 EXTENSION CORDS ARE NOT ALLOWED TO BE USED AS A SUBSTITUTE FOR PERMANENT WIRING. THE ORANGE EXTENSION CORD THAT COMES FROM INSIDE THE EAST WALL BY WINDOW MUST BE REPLACED WITH APPROVED PERMANENT WIRING. | |
05/15/2008 | INSP - FULL | Violation | 5.) TFC 703.1.1 THE MISSING CEILING TILE ABOVE POOL TABLES BY EMERGENCY EXIT NEEDS TO BE REPLACED. | |
05/15/2008 | INSP - FULL | Violation | 6.) TFC 605.6 ELECTRICAL OUTLET NEEDS A COVER PLATE. LOCATED BY SMALL SINK NEAR OFFICE. | |
05/15/2008 | INSP - FULL | Violation | 7.) TFC 904.5.1 COMMERCIAL WET CHEMICAL EXTINGUISHMENT SYSTEM IS PAST DUE FOR 6 MO. INSPECTION. | |
05/15/2008 | INSP - FULL | Violation | 8.) TFC 609.1 GREASE EXTRACTOR PANELS HAVE A GAP BETWEEN PANELS. PANELS NEED TO BE INSTALLED SO THAT NO GAPS EXIST. | |
05/15/2008 | INSP - FULL | Violation | 9.) TFC 3003.5.3 COMPRESSED GAS CYLINDER IN BACK STORAGE ROOM NEEDS TO BE SECURED TO PREVENT FALLING. | |
05/15/2008 | INSP - FULL | Violation | 10) TFC 703.1.1 TWO MISSSING CEILING TILES IN BACK STORAGE ROOM NEED TO BE REPLACED TO PROVIDE REQUIRED FIRE BLOCKING AND DRAFT STOPPING. | |
05/15/2008 | INSP - FULL | Violation | 11.) TFC 703.1.1 ADDITIONAL PANELS NEED BE ADDED AT TOP OF WALL IN BACK STORAGE ROOM TO PROVIDE FIRE BLOCKING AND DRAFT STOPPING ABOVE WALK-IN FREEZER. | |
05/15/2008 | INSP - FULL | Violation | 12.) TFC 315.2.1 BOXES AND STORAGE ON SHELVES IN BACK STORAGE ROOM NEED TO BE MOVED TO MAINTAIN 18" CLEARANCE FROM THE CEILING. | |
05/15/2008 | INSP - FULL | Violation | 13.) TFC 1011.4 EXIT SIGNS SHALL BE INTERNALLY OF EXTERNALLY ILLUMINATED AT ALL TIMES. REPAIR ALL EXIT SIGNS TO ILLUMINATE PROPERLY. | |
05/15/2008 | INSP - FULL | Violation | 14.) TFC 1006.3 EMERGENCY ILLUMINATION UMITS NEED TO BE SREVICED/REPAIRED TO OPERATE PROPERLY. |