Case: T07FR00478

Parcel: 14122004L


Addresses:

8755 S RITA RD


Inspection Status: Approved

Inspection History: INSP - AST/UST

Case Number - T07FR00478

Inspection Description - INSP - AST/UST

Inspection Status - Approved

Date Description Inspector Results Comments
08/13/2007 INSP - AST/UST Approved vent lines are in place. Door is labled and has a NFPA 704. permit issued.
03/13/2007 INSP - AST/UST Correction Required Site inspection of generator AST, needs to be vented to outside and a normal vent line added. Vent lines shall slope back to tank. Flame arresters shall be installed at end of vent lines outside of building. Tank needs to be labeled appropriately.