Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/13/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PARTIAN IN BACK STORAGE AREA |
|
| 01/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK CONDENSORS ON ROOF - RECEIVED REVISION FOR SERVICE MODIFICATIONS, CANNOT CLEAR UNTIL NEW PANEL FEEDER TIED INTO EXISTING DISCONNECT AT SERVICE. |
|
| 12/28/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NOT PER PLANS. PLANS SHOWS 400 AMP BUSHING IN WIREWAY AND THIS BUSHING DOES NOT EXIST. CANNOT JUST TAP ONE CONDUCTOR OF PARALLEL FEED TO EXISTING SERVICE 2. INSTALL MAIN BONDING JUMPER AT NEW SERVICE PANELS 3. PLEASE VERIFY GROUNDING ELECTRODE SYSTEM FOR BUILDING |